Skip to main content
Siemens 3RK1400-1CQ00-0AA3 — Remote I/O & Fieldbus Modules

Siemens 3RK1400-1CQ00-0AA3 K60 Digital I/O Module, 4 Inputs

MPN3RK1400-1CQ00-0AA3
Active

Siemens K60 compact field I/O module, 3RK1400-1CQ00-0AA3, 4 inputs / 4 outputs, PNP, IP67, 20-30 VDC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RK1400-1CQ00-0AA3 — Identification
ParameterValue
Product designdigital I/O modules for operation in the field, IP67 - K60
3RK1400-1CQ00-0AA3 — I/O
ParameterValue
Digital inputs4
3RK1400-1CQ00-0AA3 — Environmental
ParameterValue
Ingress protection (IP)IP67
Operating temperature range-25 ... +85 °C
Storage temperature range-40 ... +85 °C
Shock resistance15g / 11 ms
3RK1400-1CQ00-0AA3 — Mechanical
ParameterValue
Width60 mm
Depth29 mm
Height152 mm
Mounting methodstandard rail mounting/wall mounting using mounting plate for K60 compact module

Product details

The Siemens 3RK1400-1CQ00-0AA3 is a K60 compact digital I/O module designed for field-mounting at IP67, meaning it handles washdown environments and direct exposure on a machine frame without an enclosure. It provides 4 PNP inputs and 4 outputs, each accessible via standard M12 sockets, with the input circuit configured for PNP transistors. The module requires a 20 to 30 VDC sensor supply on PIN 1 and an external auxiliary power supply (20 to 30 VDC, PELV per VDE 0106) to drive the output circuits. This separate AUX POWER rail is a key integration point — it keeps the output drive isolated from the sensor supply, which simplifies fault isolation on the line.

Mounts on standard rail or wall via the K60 mounting plate (delivered separately). Each of the 8 M12 sockets maps a specific pinout: PIN 2 and 4 carry data input for IN1 through IN4, while PIN 4 alone carries the output signal for OUT1 through OUT4. PIN 5 on every socket ties to the grounding wrist strap in the mounting plate. Built-in watchdog, short-circuit protection, and induction suppression are included on the module, reducing the need for external protection components in the panel. Addressing is set via the front addressing socket, with a default ID/ID2 code of 0/F.

Frequently asked questions

What voltage does the module need to operate?

The module requires a 20 to 30 VDC supply on the sensor supply pin (PIN 1) and a separate 20 to 30 VDC auxiliary power supply (PELV per VDE 0106) for the output circuits.

What is the I/O configuration of this module?

It is a Type 4 inputs / 4 outputs module with PNP input circuits. The inputs are on sockets 1-4 (PIN 2/4), and the outputs are on sockets 5-8 (PIN 4).

What is the physical size and mounting method?

The module is 60 mm wide, 29 mm deep, and 152 mm high. It mounts on standard rail or wall using the K60 mounting plate (sold separately).

MPN
3RK1400-1CQ00-0AA3