Skip to main content
Siemens 3RK1400-1DQ03-0AA3 — Remote I/O & Fieldbus Modules

Siemens 3RK1400-1DQ03-0AA3 Remote I/O Module

MPN3RK1400-1DQ03-0AA3
Active

Siemens 3RK1400-1DQ03-0AA3 K60 compact digital I/O module, 4 PNP inputs / 4 outputs, IP67, 20-30 VDC, 60 x 152 x 29 mm, DIN-rail or wall-mount.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RK1400-1DQ03-0AA3 — Identification
ParameterValue
Product designdigital I/O modules for operation in the field, IP67 - K60

I/O

3RK1400-1DQ03-0AA3 — I/O
ParameterValue
Digital inputs4

Environmental

3RK1400-1DQ03-0AA3 — Environmental
ParameterValue
Ingress protection (IP)IP67
Operating temperature range-25 ... +85 °C
Storage temperature range-40 ... +85 °C
Shock resistance15g / 11 ms

Mechanical

3RK1400-1DQ03-0AA3 — Mechanical
ParameterValue
Width60 mm
Depth29 mm
Height152 mm
Mounting methodstandard rail mounting/wall mounting using mounting plate for K60 compact module

Product details

Field-mount I/O for wet or tight spaces

The Siemens 3RK1400-1DQ03-0AA3 is a K60 compact digital I/O module delivering 4 PNP inputs and 4 outputs in a sealed IP67 housing — rated for direct mounting on machine frames or in washdown zones without a secondary enclosure. It accepts 20-30 VDC on the input side, but an external auxiliary supply (20-30 VDC, PELV per VDE 0106) is required to power the output circuits — a common detail that catches first-time specifiers.

PNP inputs and M12 pinout

All four inputs are PNP transistor type, matching standard 3-wire proximity and photoelectric sensors. Each M12 socket carries the sensor supply on pin 1 (L+), data on pin 2/4, and ground on pin 3 (L-). The eight M12 sockets are pre-assigned: sockets 1-4 handle inputs IN1-IN4 on pins 2/4; sockets 5-8 handle outputs OUT1-OUT4 on pin 4 only. Pin 5 of every socket ties to the grounding wrist strap in the mounting plate.

Built-in protection and diagnostics

Short-circuit protection, induction suppression, and a watchdog timer are all integrated — no external suppression diodes or fuses needed per channel. A yellow LED per I/O and a green LED for auxiliary power give quick visual status. The module is rated for 15g shock at 11 ms and operates from -25 to +85 °C, with storage range from -40 to +85 °C.

Mounting and addressing

Mounts on standard DIN rail or directly to a wall using the K60 mounting plate (supplied separately — the module ships without it). Dimensions are 60 mm wide, 152 mm high, 29 mm deep. Addressing is set via a front socket; the ID/ID2 code is 0/F. The I/O configuration code is 7.

Frequently asked questions

What is the IP rating and where can this module be mounted?

IP67 rated, meaning it is dust-tight and protected against temporary immersion. It is designed for direct field mounting on machine frames or in wet environments without an enclosure, using DIN rail or the K60 mounting plate.

What type of inputs does it have — PNP or NPN?

All four inputs are PNP transistor type, compatible with standard 3-wire PNP sensors (proximity, photoelectric, etc.).