Skip to main content
Siemens 3RK1400-2CE00-2AA2 — Remote I/O & Fieldbus Modules

Siemens 3RK1400-2CE00-2AA2 AS-i SC22.5, 4DI/4DQ, Standard

MPN3RK1400-2CE00-2AA2
Active

Siemens Slimline SC22.5, 3RK1400-2CE00-2AA2, AS-Interface I/O module, 4 digital inputs PNP Type 2, 4 digital outputs PNP, IP20, 22.5 mm wide.

$124.46Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RK1400-2CE00-2AA2 — Identification
ParameterValue
Product designationSlimline Compact I/O module for use in the control cabinet
Product designAS-i SC22.5, 4DI/4DQ, Standard
3RK1400-2CE00-2AA2 — Communication
ParameterValue
AS-Interface supportYes
3RK1400-2CE00-2AA2 — I/O
ParameterValue
Digital inputs4
3RK1400-2CE00-2AA2 — Environmental
ParameterValue
Ingress protection (IP)IP20
Operating temperature range-25 ... +70 °C
Storage temperature range-40 ... +85 °C
Shock resistance15g / 11 ms (modules) or 10g / 11 ms (modules with device connector)
3RK1400-2CE00-2AA2 — Mechanical
ParameterValue
Width22.5 mm
Depth120 mm
Height100 mm
Mounting methodscrew and snap-on mounting

Product details

The Siemens 3RK1400-2CE00-2AA2 is an AS-Interface Slimline SC22.5 I/O module providing 4 digital inputs (PNP Type 2) and 4 digital outputs (PNP transistor) in a 22.5 mm wide housing for control-cabinet use. The slave profile is S-7.0.F, and the module is a standard slave with a factory-set, changeable ID1 code of F. Output circuits require an auxiliary external feed (AUX POWER) of 20 to 30 V DC, compliant with IEC 60990 (PELV), protection class III.

The module draws 200 mA when supplied solely via the AS-Interface bus, or 500 mA when an auxiliary supply (Uaux) is used — this matters for sizing the AS-i power supply and the AUX PELV supply. The 22.5 mm width and screw/snap-on mounting to DIN rail make it a tight fit for dense panels; depth is 120 mm, so verify clearance to the enclosure door or rear wall. Operating temperature range is -25 to +70 °C, with storage from -40 to +85 °C; shock resistance is 15g / 11 ms for the module alone, 10g / 11 ms with the device connector fitted.

Wiring and connection notes

Terminals accept 1x (0.5 to 2.5 mm²) or 2x (0.5 to 1.5 mm²) solid conductors; finely stranded with ferrules takes 1x (0.25 to 2.5 mm²) or 2x (0.25 to 1.0 mm²). AWG solid equivalents are 1x (24 to 14) or 2x (24 to 16). Stranded AWG is not permitted. Address setting is via the front addressing socket; input/output status is shown by yellow/red LEDs. The module supports 2- and 3-wire connection technology.

No official successor has been announced; the 3RK1400-2CE00-2AA2 remains the active order code for this AS-i SC22.5 4DI/4DQ standard slave configuration.

Frequently asked questions

What auxiliary supply does this module need?

An external AUX POWER supply of 20 to 30 V DC is required for the output circuits, and it must comply with IEC 60990 (PELV), protection class III.

What is the module's current draw from the AS-Interface bus?

The module draws 200 mA when supplied via the AS-Interface bus alone, or 500 mA when an auxiliary supply (Uaux) is used.

What is the physical size of this module?

It is 22.5 mm wide, 100 mm high, and 120 mm deep, with screw and snap-on mounting to DIN rail.

MPN
3RK1400-2CE00-2AA2