Skip to main content
Siemens 3RK1402-0BG00-0AA2 — Remote I/O & Fieldbus Modules

Siemens 3RK1402-0BG00-0AA2 AS-Interface SlimLine, 2I/2O rela

MPN3RK1402-0BG00-0AA2

Siemens AS-Interface SlimLine S22.5 standard slave, 2 digital inputs (PNP), 2 relay changeover outputs, IP20, 22.5 mm wide, 20-30 VDC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RK1402-0BG00-0AA2 — Identification
ParameterValue
Product designSlimLine S22.5 - I/O modules for operation in the control cabinet, IP20
3RK1402-0BG00-0AA2 — Communication
ParameterValue
AS-Interface supportYes
3RK1402-0BG00-0AA2 — I/O
ParameterValue
Digital inputs2
3RK1402-0BG00-0AA2 — Environmental
ParameterValue
Ingress protection (IP)IP20
Operating temperature range-25 ... +70°C
Storage temperature range-40 ... +85°C
3RK1402-0BG00-0AA2 — Mechanical
ParameterValue
Width22.5mm
Depth86mm
Height103mm
Mounting method35 mm standard rail mounting or wall mounting using push-in lugs

Product details

AS-Interface I/O module for the control cabinet

The Siemens 3RK1402-0BG00-0AA2 is an AS-Interface standard slave module in the SlimLine S22.5 design, sized for control-cabinet mounting on 35 mm standard rail or wall mounting using push-in lugs. It provides 2 digital inputs (PNP transistor circuit, 20-30 VDC supply) and 2 digital outputs via relay changeover contacts, floating. The module is addressed through a front addressing socket; ID/ID2 code is 0/F. A built-in watchdog monitors communication, and the AS-Interface green LED confirms bus health. Input voltage range is 20-30 VDC.

The 2 inputs are PNP only — ensure your sensors source positive to the module; NPN sensors need an interface. The relay outputs are changeover floating contacts rated 1 A at 24 V, 0.2 A at 110 V, and 0.1 A at 230 V, so they suit signal-level switching or low-power loads, not motor contactor coils directly. The module requires an external 6 A gL/gG backup fuse for short-circuit protection. With IP20 protection, it belongs inside an enclosure, not on the machine frame.

Wiring uses 2-wire technology with spring-loaded terminals accepting 2 x (0.25-1.5) mm² solid or 2 x (0.25-1) mm² with end sleeve; AWG 24-16 stranded. A detachment tool is listed as an accessory. Status indication: yellow LEDs for I/O states, red LED for fault, green for AS-Interface bus.

Frequently asked questions

What are the digital input specifications?

The module has 2 digital inputs using PNP transistor circuit, with an input voltage range of 20-30 VDC. Signal 1 minimum is 5 mA; signal 0 maximum is 1.5 mA.

What type of outputs does this module have?

It has 2 digital outputs using relay changeover floating contacts, rated 1 A at 24 V, 0.2 A at 110 V, and 0.1 A at 230 V.

What is the mounting and wiring method?

It mounts on 35 mm standard rail or wall using push-in lugs. Wiring uses 2-wire spring-loaded terminals accepting 2 x (0.25-1.5) mm² solid or 2 x (0.25-1) mm² with end sleeve.

What is the protection class and operating temperature?

Protection class is IP20, suitable for control cabinet use only. Operating temperature range is -25 to +70 °C; storage -40 to +85 °C.

Does this module require external fusing?

Yes, an external back-up fuse of 6 A gL/gG is required for short-circuit protection.

MPN