Skip to main content
Siemens 3RK1901-1NR20 — Remote I/O & Fieldbus Modules

Siemens 3RK1901-1NR20 AS-i M12 Branch, IP67/68/69K, 4A

MPN3RK1901-1NR20

Siemens 3RK1901-1NR20 AS-Interface M12 branch, U_ASI and Uaux, 1x M12 socket, IP67/68/69K, 4 A max, insulation-piercing flat-cable transition.

$41.15Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RK1901-1NR20 — Identification
ParameterValue
Product designAS-i M12 feeder, AS-i with Uaux, M12 socket
3RK1901-1NR20 — Other specifications
ParameterValue
Notecable must not end in the feeder
FunctionAS-i flat cable transition to M12
Connection1x M12 socket
Number sockets1
Type of deviceAS-Interface accessories
Type of mountingscrew fixing
Operating temperature-25 ... +75°C
IP ratingIP67/68/69K
Contacts load rating max4A
Inputs socket assignment1 = AS-i "+" 2 = Uaux "-" 3=AS-i "-" 4 = Uaux "+"
Type of electrical connectioninsulation piercing method for AS-Interface flat cable
Ambient temperature during storage-25 ... +85°C
Operating voltage according to AS-Interface spezification26.5 ... 31.6V

Product details

What this M12 branch does

The 3RK1901-1NR20 is an AS-Interface flat-cable transition to an M12 socket — it taps the AS-i bus (26.5–31.6 V) and the auxiliary power (Uaux) from the flat cable and brings them out to a single M12 female connector. Pinout is fixed: pin 1 = AS-i +, pin 2 = Uaux –, pin 3 = AS-i –, pin 4 = Uaux +. That means a standard M12 cordset gives you both the bus signal and a separate 24 V auxiliary supply in one connector — no need for a second drop.

IP rating and mounting reality

Rated IP67/68/69K — the housing and the M12 socket withstand high-pressure washdown and temporary submersion, so it fits food-and-bev, washdown, or outdoor conveyor lines where a standard IP67 module would fail under a hose-down cycle. Mounts with screw fixing, not DIN-rail snap-on. Plan for a drilled panel or bracket — the flat cable runs through the insulation-piercing gland, and the branch body bolts down.

Current and temperature limits

Contacts rated 4 A max — enough for a small actuator or sensor cluster on the auxiliary supply, but not for a motor or heater load. The branch is a signal-and-power tap, not a power distribution block. Ambient operating range –25 to +75 °C, storage –25 to +85 °C.

Frequently asked questions

How can I order 3RK1901-1NR20 or check stock?

Sourced to order against the BOM quantity. No stock-holding claim is made here.

What does the note 'cable must not end in the feeder' mean?

It means the AS-i flat cable should not terminate inside this branch module — the cable passes through the insulation-piercing connection and continues to the next drop. The branch is a tap, not a cable end.

What is the function of 3RK1901-1NR20?

It transitions the AS-i flat cable to a single M12 socket, carrying both AS-i bus voltage and auxiliary power (Uaux) on the same connector. Pinout: pin 1 = AS-i +, pin 2 = Uaux –, pin 3 = AS-i –, pin 4 = Uaux +.

MPN