Siemens 3RK1904-2AB01 — Remote I/O & Fieldbus Modules

Siemens 3RK1904-2AB01 AS-Interface Addressing Unit, IP50

MPN3RK1904-2AB01

Siemens 3RK1904-2AB01 AS-Interface addressing and diagnostic unit, IP50, battery-powered, M12 socket connection, 195 x 84 x 35 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RK1904-2AB01 — Identification
ParameterValue
Product designAS-Interface addressing unit
3RK1904-2AB01 — Environmental
ParameterValue
Operating temperature range0 ... 55°C
Storage temperature range-20 ... +55°C
3RK1904-2AB01 — Mechanical
ParameterValue
Width84mm
Depth35mm
Height195mm
3RK1904-2AB01 — Other specifications
ParameterValue
DeviceIP50
Connectionusing M12 socket: Pin1=AS-i+; Pin3=AS-i-/GND; Pin2/4/5=IR-addressing
Power supplyis provided by 4 batteries according to IEC LR6 (NEDA 15), which guarantee that the unit can perform at least 2500 device addressings. For a longer battery life the unit is switched off automatically approx. 1 minute after the last operation
Connection socketIP20
Other informationstorage temperature without batteries
Conditions of applicationonly in indoor rooms
Rated operational current ie100mA
Environmental conditions relative humiditymax. 75 %, condensation not permitted

Product details

The Siemens 3RK1904-2AB01 is a handheld AS-Interface addressing and diagnostic unit for active AS-i modules and intelligent sensors/actuators compliant with AS-Interface specification V2.1. It connects to the target device through an M12 socket with a defined pinout: Pin 1 carries AS-i+, Pin 3 carries AS-i-/GND, and Pins 2, 4, and 5 are reserved for IR addressing. Power comes from four LR6 (NEDA 15) batteries, good for at least 2500 device addressings per set; the unit auto-powers off about one minute after the last operation to conserve battery life.

The IP50 rating means the housing is dust-protected but not sealed against water — this is strictly an indoor tool for dry environments like control cabinets or commissioning benches. Operating temperature range of 0 to 55 °C covers most plant-floor conditions; storage range of -20 to +55 °C (without batteries) is fine for the service van between jobs. The 100 mA rated operational current is the unit's own draw during addressing — negligible for the battery budget, but it tells you the M12 connection isn't powering anything else.

Frequently asked questions

What is the 3RK1904-2AB01 used for?

It is an AS-Interface addressing and diagnostic unit used to set addresses on active AS-i modules and intelligent sensors/actuators compliant with AS-Interface V2.1.

Does the 3RK1904-2AB01 work with the 6ES7211-1HD30-0XB0 or similar PLCs?

No — this is a standalone AS-Interface addressing tool, not a PLC module. It does not drop into a panel or replace any SIMATIC S7-1200 CPU.