Skip to main content
Siemens 3RK2100-1CT30-0AA3 — Remote I/O & Fieldbus Modules

Siemens 3RK2100-1CT30-0AA3 AS-i K20 Module, 4 Outputs, 2 A,

MPN3RK2100-1CT30-0AA3
Active

Siemens AS-Interface K20 digital output module, 3RK2100-1CT30-0AA3, 4 PNP outputs, 2 A max, IP67, for field I/O.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RK2100-1CT30-0AA3 — Identification
ParameterValue
Product designdigital I/O modules for operation in the field, IP67 - K20
3RK2100-1CT30-0AA3 — I/O
ParameterValue
Digital inputs0
3RK2100-1CT30-0AA3 — Environmental
ParameterValue
Ingress protection (IP)IP67
Operating temperature range-25 ... +70 °C
Storage temperature range-40 ... +85 °C
Shock resistance15g / 11 ms
3RK2100-1CT30-0AA3 — Mechanical
ParameterValue
Width20 mm
Depth45 mm
Height108 mm
Mounting methodno mounting plate required

Product details

AS-i Field Output Module, 4-Channel

The Siemens 3RK2100-1CT30-0AA3 is a K20 digital output module for AS-Interface networks, delivering 4 PNP transistor outputs rated at 2 A total at 40 °C. It requires an external 20–30 V DC auxiliary power supply (PELV per VDE 0106, protection class III) to drive the output circuits — the AS-i bus cable alone cannot supply the load current. The module is a full A/B slave compliant with AS-i Specification 3.0, with an ID/ID2 code of A/7 and an I/O configuration of 7. Built for direct field mounting, the IP67 housing (108 × 45 × 20 mm) needs no backplate and accepts M12 connectors for both the AS-i bus and the external AUX supply. Four M12 sockets each map pin 4 to one output (OUT1–OUT4), with pin 3 wired to the common negative. Integrated short-circuit protection, induction suppression, and a watchdog are standard — no external clamp diodes or fuses needed per channel.

This order code is in its current lifecycle stage — still active in the Siemens AS-Interface portfolio.

Integration Notes

Operates from –25 to +70 °C, stores from –40 to +85 °C, and withstands 15 g shock at 11 ms — rugged enough for conveyor-adjacent or washdown-zone mounting. The AS-i bus draws 45 mA from the master; the output load current comes entirely from the external 24 V DC AUX feed, so plan a separate PELV supply in the panel. Yellow LEDs per output and a green LED for AUX power give quick status at the module face; the dual red/green AS-i LED reports bus communication and diagnostics. No mounting plate is required — the module clips directly to a machine frame or bracket.

Frequently asked questions

What are the key ratings for this module?

It has 4 PNP digital outputs, a total module current of 2 A at 40 °C, an AS-i bus current draw of 45 mA, and requires an external 20–30 V DC auxiliary supply for the output circuits. The housing is IP67 rated.

Does this module need an external power supply?

Yes, an external 20–30 V DC PELV supply (AUX POWER) is mandatory to power the output circuits. The AS-interface cable only provides bus communication and module electronics power.

How do I source this part?

The module is quoted to order against an RFQ. Provide your quantity and required delivery window, and we will confirm availability and pricing from our supply channel.

MPN
3RK2100-1CT30-0AA3