Skip to main content
Siemens 3RK2200-0CG00-2AA2 — Remote I/O & Fieldbus Modules

Siemens 3RK2200-0CG00-2AA2 AS-i Slimline I/O Module, 4DI

MPN3RK2200-0CG00-2AA2
Active

Siemens Slimline AS-Interface I/O module, 3RK2200-0CG00-2AA2, 4 digital inputs PNP Type 2, 17.5 mm width, IP20, spring-loaded terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RK2200-0CG00-2AA2 — Identification
ParameterValue
Product designationSlimline Compact I/O module for use in the control cabinet
Product designAS-i SC17.5, 4DI A/B, 2-wire
3RK2200-0CG00-2AA2 — Communication
ParameterValue
AS-Interface supportYes
3RK2200-0CG00-2AA2 — I/O
ParameterValue
Digital inputs4
3RK2200-0CG00-2AA2 — Environmental
ParameterValue
Ingress protection (IP)IP20
Operating temperature range-25 ... +70 °C
Storage temperature range-40 ... +85 °C
Shock resistance15g / 11 ms (modules) or 10g / 11 ms (modules with device connector)
3RK2200-0CG00-2AA2 — Mechanical
ParameterValue
Width17.5 mm
Depth120 mm
Height100 mm
Mounting methodscrew and snap-on mounting

Product details

The Siemens 3RK2200-0CG00-2AA2 is a Slimline Compact I/O module for control cabinet use, designed as an AS-i SC17.5 slave with 4 digital inputs (PNP Type 2) and no outputs. Communication runs over the AS-Interface protocol, with the slave profile set to S-0.A.0. The module is an A/B slave type, addressable via the front addressing socket; the ID1 code ships at factory setting 7 but is changeable in the field.

The four digital inputs are PNP Type 2 per EN 61131-2, which means they sink current from a positive sensor supply — standard for most 3-wire proximity and photoelectric sensors in European panels. The sensor supply is short-circuit and overload resistant, rated for 200 mA total at 40 °C ambient, so you can power a handful of small sensors directly without an external distribution block. Operating voltage comes from the AS-Interface bus itself, spanning 18 to 31.6 V per the AS-Interface specification. The module also supports AS-i Power24V, drawing up to 270 mA at 24 V — useful if your network already uses that power supply variant. The AS-Interface bus supplies up to 2 A total for the module's needs. Spring-loaded terminals accept solid or stranded wire from 0.5 to 1.5 mm² (20–16 AWG), and finely stranded wire with ferrule from 0.25 to 1.0 mm². The 2-wire connection technology keeps field wiring simple — just two wires per input, no separate supply pair needed. Rated IP20, so this module belongs inside a sealed control cabinet — not on the machine frame or in washdown zones. Shock resistance is 15g / 11 ms for the module alone, or 10g / 11 ms with the device connector attached.

Frequently asked questions

What is the module's width and how does it mount?

The housing is 17.5 mm wide, 100 mm tall, and 120 mm deep. It mounts via screw and snap-on fastening to a standard DIN rail — no adapter plate required.

What wire sizes does the spring terminal accept?

Solid or stranded: 1x or 2x conductors from 0.5 to 1.5 mm² (20–16 AWG). Finely stranded with ferrule: 0.25 to 1.0 mm². No special tools beyond a screwdriver for the spring release.

Can this module run on AS-i Power24V?

Yes, it is explicitly suitable for AS-i Power24V. At 24 V the maximum current draw is 270 mA.

How do I address this AS-i slave?

Addressing is done via the front addressing socket. The module is an A/B slave type, and the ID1 code is factory-set to 7 but can be changed.

MPN