Skip to main content
Siemens 3RK2200-0CU20-0AA3 — Remote I/O & Fieldbus Modules

Siemens 3RK2200-0CU20-0AA3 AS-Interface K45 Module, 4 PNP In

MPN3RK2200-0CU20-0AA3

Siemens AS-Interface K45 compact module, 3RK2200-0CU20-0AA3, 4 digital PNP inputs, IP65, current production lifecycle.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RK2200-0CU20-0AA3 — Identification
ParameterValue
Product designdigital I/O modules for operation in the field, IP65 - K45
3RK2200-0CU20-0AA3 — I/O
ParameterValue
Digital inputs4
3RK2200-0CU20-0AA3 — Environmental
ParameterValue
Ingress protection (IP)IP65
Operating temperature range-25 ... +85 °C
Storage temperature range-40 ... +85 °C
Shock resistance15g / 11 ms
3RK2200-0CU20-0AA3 — Mechanical
ParameterValue
Width45 mm
Depth30 mm
Height80 mm
Mounting methodstandard rail mounting/wall mounting using mounting plate for K45 compact module

Product details

The 3RK2200-0CU20-0AA3: Each of the four input sockets accepts a 2- or 3-wire PNP sensor; PIN 4 on each socket is the data line (D0–D3), with PIN 1 and PIN 3 carrying sensor supply L+ and L- from the AS-Interface bus. The module draws up to 270 mA total from the AS-Interface line, and the sensor supply is short-circuit and overload protected — handy when a prox gets whacked on a conveyor line.

Front addressing socket sets the slave ID; the module ships without a mounting plate, so grab one if you're wall-mounting rather than snapping onto DIN rail. Inputs switch high above 10 V, with a minimum signal-1 current of 6 mA and signal-0 leakage under 1.5 mA. Yellow LEDs on each input give a quick visual on I/O state; the green/red dual LED reports AS-Interface communication and diagnostics.

Frequently asked questions

Where can I buy 3RK2200-0CU20-0AA3?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the input type and count on this module?

It has 4 digital inputs, PNP transistor type, designed for 2- and 3-wire sensors, with a switching level high minimum of 10 V.

Will 3RK2200-0CU20-0AA3 drop into a panel specified around 3RT1023-1AL20 without rewiring?

No — 3RT1023-1AL20 is a contactor, not an AS-Interface I/O module. This K45 module is a completely different device class and footprint; it won't interchange without a full rewiring and network reconfiguration.

MPN
3RK2200-0CU20-0AA3