Skip to main content
Siemens 3RK2200-2CE00-2AA2 — Remote I/O & Fieldbus Modules

Siemens 3RK2200-2CE00-2AA2 AS-i SC22.5 4DI Module, IP20

MPN3RK2200-2CE00-2AA2
Active

Siemens Slimline SC22.5, 4DI A/B, 3-wire, AS-Interface I/O module, 22.5 mm width, IP20, 200 mA via AS-i / 500 mA via Uaux.

$105.41Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RK2200-2CE00-2AA2 — Identification
ParameterValue
Product designationSlimline Compact I/O module for use in the control cabinet
Product designAS-i SC22.5, 4DI A/B, 3-wire
3RK2200-2CE00-2AA2 — Communication
ParameterValue
AS-Interface supportYes
3RK2200-2CE00-2AA2 — I/O
ParameterValue
Digital inputs4
3RK2200-2CE00-2AA2 — Environmental
ParameterValue
Ingress protection (IP)IP20
Operating temperature range-25 ... +70 °C
Storage temperature range-40 ... +85 °C
Shock resistance15g / 11 ms (modules) or 10g / 11 ms (modules with device connector)
3RK2200-2CE00-2AA2 — Mechanical
ParameterValue
Width22.5 mm
Depth120 mm
Height100 mm
Mounting methodscrew and snap-on mounting

Product details

AS-i SC22.5 4DI Module — Fit and Supply

The Siemens 3RK2200-2CE00-2AA2 is a Slimline Compact I/O module for control-cabinet use, part of the AS-i SC22.5 family. It provides 4 digital inputs (PNP Type 2) in a 22.5 mm wide housing, with a depth of 120 mm and height of 100 mm. The module is an A/B slave with profile S-0.A.0, supporting 2- and 3-wire sensor technology. Current draw depends on the supply source: 200 mA when powered via the AS-Interface bus, or 500 mA when an auxiliary external feed (Uaux) between 20 and 30 V DC is used. That auxiliary feed is mandatory for powering output circuits and must comply with IEC 60990 (PELV), protection class III. The module also supports AS-i Power24V, drawing 270 mA at 24 V in that configuration. The IP20 rating means it's intended for dry, enclosed control cabinets, not washdown environments.

Shock resistance is 15g / 11 ms for the module alone, or 10g / 11 ms with a device connector attached.

Wiring and Addressing

Terminals accept solid conductors: 1x (0.5 to 2.5 mm²) or 2x (0.5 to 1.5 mm²). For AWG, solid 1x (24 to 14) or 2x (24 to 16). Finely stranded with core-end processing: 1x (0.25 to 2.5 mm²) or 2x (0.25 to 1.0 mm²). Stranded without ferrules is not permitted. Address setting is via the front addressing socket; the factory-set ID1 code is 7, changeable. Input status is indicated by yellow LEDs. The module has 0 analog inputs and 0 analog outputs — purely digital I/O. No safety-related digital inputs are present.

Frequently asked questions

Where can I buy 3RK2200-2CE00-2AA2?

This module is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the current draw of 3RK2200-2CE00-2AA2?

It draws 200 mA when supplied via the AS-Interface bus, or 500 mA when using the auxiliary external feed (Uaux). With AS-i Power24V at 24 V, draw is 270 mA.

Does 3RK2200-2CE00-2AA2 require an external power supply?

Yes, an auxiliary external feed (AUX POWER) between 20 and 30 V DC is necessary for supplying the output circuits. It must comply with IEC 60990 (PELV), protection class III.

What is the depth of 3RK2200-2CE00-2AA2?

The module depth is 120 mm, with a width of 22.5 mm and height of 100 mm.

MPN
3RK2200-2CE00-2AA2