Skip to main content
Siemens 3RK4320-3AQ54-0BA2 — Motor Starters

Siemens 3RK4320-3AQ54-0BA2 Motor Starter, 0.63 A, CLASS 10

MPN3RK4320-3AQ54-0BA2

Siemens SIRIUS 3RK4320-3AQ54-0BA2 motor starter MCU for AS-Interface, direct starter, 0.63 A at 400 V AC-3, CLASS 10, IP54, 205 x 245 x 215 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RK4320-3AQ54-0BA2 — Identification
ParameterValue
Product designationmotor starter MCU for AS-Interface
Main circuit poles3
BrandSIRIUS
Product design / constructiondirect starter
Reference designation (IEC 81346-2)Q
3RK4320-3AQ54-0BA2 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Overload release setting range (current)0.45 ... 0.63 A
Duty / utilization type (IEC 60947-6-2)1
3RK4320-3AQ54-0BA2 — Contacts & Control
ParameterValue
Switching contact typeelectromechanical
3RK4320-3AQ54-0BA2 — Communication
ParameterValue
AS-Interface protocol supportYes
3RK4320-3AQ54-0BA2 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
Width245 mm
Height215 mm
Depth205 mm

Product details

SIRIUS motor starter for AS-Interface networks

The 3RK4320-3AQ54-0BA2: It integrates motor protection, switching, and communication into a single device, reducing wiring and panel space compared to a contactor-plus-overload-relay combination. The 3-pole main circuit handles the motor current, while the control supply runs on 20.4–26.4 V DC.

Panel fit and mounting flexibility

Dimensions are 205 mm deep, 245 mm wide, and 215 mm high — a compact footprint for a motor starter with integrated bus communication and brake output. The unit mounts on a vertical surface and allows ±180° rotation and ±22.5° forward/backward tilt, giving flexibility in tight enclosures. Rated IP54, so it handles dust and splashing water in industrial environments.

AS-Interface integration and brake control

The starter communicates via AS-Interface protocol (no PROFIBUS or PROFINET onboard), with 2 digital inputs for local sensors or pushbuttons. It includes a motor brake output, allowing direct control of a holding brake without an external relay. Short-circuit protection is designed for use with circuit-breakers upstream, and the switching contacts are electromechanical — not solid-state. The unit is rated for up to 80 operating cycles per hour, which covers most conveyor and pump cycling applications.

Frequently asked questions

What is the rated current of 3RK4320-3AQ54-0BA2 at 400 V?

It is rated 0.63 A at 400 V in both AC-3 (motor switching) and general AC duty. This is a low-current motor starter for small motors or fractional-horsepower loads.

Does 3RK4320-3AQ54-0BA2 support PROFINET or PROFIBUS?

No, it supports AS-Interface only. PROFINET and PROFIBUS DP are both listed as not supported.

MPN
3RK4320-3AQ54-0BA2