Siemens SIRIUS 3RK4353-3ER58-1BA0 reversing motor starter, 1.6 A at 400 V AC-3, Trip Class 10, IP55, 3-pole, AC coil 184-253 V 50 Hz / 196-253 V 60 Hz.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RK4353-3ER58-1BA0 — Identification
ParameterValue
Product designationmotor starter MCU controlled on site
Main circuit poles3
BrandSIRIUS
Product design / constructionreversing starter
Reference designation (IEC 81346-2)Q
3RK4353-3ER58-1BA0 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Overload release setting range (current)1.1 ... 1.6 A
Duty / utilization type (IEC 60947-6-2)1
3RK4353-3ER58-1BA0 — Contacts & Control
ParameterValue
Rated voltage range at 50 Hz184 ... 253 V
Switching contact typeelectromechanical
3RK4353-3ER58-1BA0 — Communication
ParameterValue
AS-Interface protocol supportNo
3RK4353-3ER58-1BA0 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
Width182 mm
Height220 mm
Depth145 mm

Product details

Reversing starter with local intelligence

The 3RK4353-3ER58-1BA0: The MCU-controlled on-site design gives it two digital inputs for local start/stop or interlock signals, but no fieldbus connection — this is a standalone reversing starter for simple forward/reverse control of a conveyor, pump, or fan where you don't need PROFINET or PROFIBUS.

Mounting and environment constraints

The enclosure measures 145 mm deep × 182 mm wide × 220 mm high — that's a compact footprint for a reversing starter, but the IP55 rating means it's sealed against dust jets and low-pressure water spray, so it can live on the machine frame in a washdown area or dusty mill environment.

Coil supply and short-circuit coordination

The AC coil accepts 184...253 V at 50 Hz and 196...253 V at 60 Hz — that covers standard 230 V control circuits across both line frequencies. Operating voltage for the power circuit is 340...440 V, so it's at home on 400 V nominal three-phase systems. Short-circuit protection is designed for circuit-breakers upstream — the starter itself has no integral SCCR rating listed, so coordinate the upstream breaker per Siemens' selectivity tables to keep the fault energy within the starter's withstand. The 3-pole main current circuit handles the three-phase motor load.

Frequently asked questions

What is the 1.6 A rating at 400 V AC-3 for this motor starter?

The 1.6 A at 400 V AC-3 is the motor full-load current the starter can switch under AC-3 duty (starting and stopping motors). It's the same value as the AC at 400 V rated value — both are 1.6 A.

MPN