Skip to main content
Siemens 3RK4353-3FR58-1BA0 — Motor Starters

Siemens 3RK4353-3FR58-1BA0 SIRIUS Reversing Starter

MPN3RK4353-3FR58-1BA0

Siemens SIRIUS reversing motor starter, MCU-controlled on site, 3RK4353-3FR58-1BA0, CLASS 10, 2 A at AC-3 400 V, IP55, 3-pole, 145 x 182 x 220 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RK4353-3FR58-1BA0 — Identification
ParameterValue
Product designationmotor starter MCU controlled on site
Main circuit poles3
BrandSIRIUS
Product design / constructionreversing starter
Reference designation (IEC 81346-2)Q
3RK4353-3FR58-1BA0 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Overload release setting range (current)1.4 ... 2 A
Duty / utilization type (IEC 60947-6-2)1
3RK4353-3FR58-1BA0 — Contacts & Control
ParameterValue
Rated voltage range at 50 Hz184 ... 253 V
Switching contact typeelectromechanical
3RK4353-3FR58-1BA0 — Communication
ParameterValue
AS-Interface protocol supportNo
3RK4353-3FR58-1BA0 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
Width182 mm
Height220 mm
Depth145 mm

Product details

It's a 3-pole electromechanical starter rated 2 A at AC-3 400 V, with bimetal motor protection and a CLASS 10 trip curve.

The 2 A at AC-3 400 V rating governs the motor-switching capability — AC-3 is the standard duty category for starting squirrel-cage induction motors and disconnecting them while running. For a 400 V line, 2 A AC-3 translates to roughly 1.1 kW motor load (standard 3-phase induction motor).

Mounting and environment — built for the nacelle or the washdown zone

The IP55 rating means dust-protected and protected against water jets — this starter survives hose-down cleaning and condensation common in food processing, wastewater, or turbine nacelles. Ambient range of -25 to +35 °C covers unheated enclosures in temperate climates, but if your enclosure runs above 35 °C, you'll need to derate or force ventilation.

Frequently asked questions

Where can I buy the Siemens 3RK4353-3FR58-1BA0 reversing starter?

This part is sourced to order; availability and pricing are confirmed at quote time. Contact our sales team for current lead time and pricing.

MPN
3RK4353-3FR58-1BA0