Skip to main content
Siemens 3RK4353-3JR58-0BA0 — Motor Starters

Siemens 3RK4353-3JR58-0BA0 SIRIUS Motor Starter, 4 A AC-3

MPN3RK4353-3JR58-0BA0

Siemens SIRIUS 3RK4353-3JR58-0BA0 direct motor starter, MCU controlled on site, 4 A AC-3 at 400 V, Class 10 bimetal protection, IP55, 145 x 182 x 220 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RK4353-3JR58-0BA0 — Identification
ParameterValue
Product designationmotor starter MCU controlled on site
Main circuit poles3
BrandSIRIUS
Product design / constructiondirect starter
Reference designation (IEC 81346-2)Q
3RK4353-3JR58-0BA0 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Overload release setting range (current)2.8 ... 4 A
Duty / utilization type (IEC 60947-6-2)1
3RK4353-3JR58-0BA0 — Contacts & Control
ParameterValue
Rated voltage range at 50 Hz184 ... 253 V
Switching contact typeelectromechanical
3RK4353-3JR58-0BA0 — Communication
ParameterValue
AS-Interface protocol supportNo
3RK4353-3JR58-0BA0 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
Width182 mm
Height220 mm
Depth145 mm

Product details

Motor starting duty and protection profile

The 3RK4353-3JR58-0BA0: The Class 10 bimetal overload relay trips within 10 seconds at 600% of the set current, which protects standard squirrel-cage motors during stall or jam conditions without nuisance trips on normal acceleration. The electromechanical switching contact handles the inrush, and the integrated short-circuit protection via circuit-breakers means the starter coordinates with an upstream breaker for Type 2 coordination — the starter survives a fault without welding its contacts.

Panel fit and environmental limits

The IP55 enclosure means it handles dust and water jets — suitable for washdown areas in food processing or outdoor installations under a canopy, but not submersion.

Supply voltage and operating frequency

The operating voltage range is 340–440 V AC, with the control supply rated 184–253 V at 50 Hz and 196–253 V at 60 Hz. Maximum operating frequency is 80 operations per hour — that's the thermal limit of the bimetal element resetting between starts. For higher cycling rates, you'd need an electronic overload or a different starter design.

Sourcing and compliance posture

Substance prohibitance date is 05/01/2012, indicating RoHS compliance from that date forward. The reference code per IEC 81346-2 is Q, which classifies it as a switching device in the plant documentation system.

MPN
3RK4353-3JR58-0BA0