Skip to main content
Siemens 3RK5010-0BA10-0AA0 — Motor Starters

Siemens 3RK5010-0BA10-0AA0 IO-Link Module K20

MPN3RK5010-0BA10-0AA0

Siemens 3RK5010-0BA10-0AA0 IO-Link module K20, 4 digital inputs, 2 I/O sockets, IP67, 200 mA sensor supply per socket, 24 VDC, 45x20x108 mm.

StockContact for availability
Lead time1-2 Weeks wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RK5010-0BA10-0AA0 — Identification
ParameterValue
Product designationIO-Link module K20
Product design / construction4 digital inputs

Mechanical & Connection

3RK5010-0BA10-0AA0 — Mechanical & Connection
ParameterValue
Mounting / fastening methodfrontal or lateral wall mounting
Width20mm
Height108mm
Depth45mm

Environmental

3RK5010-0BA10-0AA0 — Environmental
ParameterValue
Operating temperature range-25 ... +70°C
Storage temperature range-40 ... +85°C

Product details

IO-Link module K20 — four digital inputs in an IP67 slice

The 3RK5010-0BA10-0AA0 is a Siemens IO-Link module K20, a compact field-mount slice that brings four digital inputs (PNP, Y-assignment pinout) to a motor starter or sensor network without pulling wires back to a central cabinet. Each of the two M12 sockets supplies up to 200 mA to its paired sensor (pin 1 = sensor supply +, pin 3 = sensor supply -), with the input signal on pin 4 (IN1/IN3) and a second input on pin 2 (IN2/IN4). The IP67 rating means the module lives directly on the machine frame or conveyor section, not inside a panel — frontal or lateral wall mounting keeps it out of the washdown spray path while staying accessible for cable swaps.

Input timing and diagnostics you can tune per channel

Input delay is adjustable per module at 1 ms, 3 ms, 15 ms, or 20 ms — useful for debouncing a mechanical limit switch on one channel while keeping a fast proximity sensor on another at the 1 ms setting. Signal inversion is also adjustable per input, so a normally-closed safety guard switch can be read as a logic 1 without external inversion wiring. The module reports overload, short-circuit, and internal errors via IO-Link diagnostics — the green/red dual LED on the link device gives a quick visual on communication health without plugging in a laptop.

Current production — quoted to order against BOM quantities

Sourced through authorized distribution channels; availability and volume pricing confirmed at RFQ against the BOM line.

Frequently asked questions

What is the 3RK5010-0BA10-0AA0 used for?

It is an IO-Link module K20 that adds four digital inputs to a motor starter or sensor network in an IP67 field-mount housing. It connects to two M12 sockets, each supplying 200 mA to its paired sensor, and communicates input status and diagnostics over IO-Link.

Can 3RK5010-0BA10-0AA0 replace 6ES7193-4CC30-0AA0 in an existing panel?

No direct drop-in replacement is documented. The 6ES7193-4CC30-0AA0 is a different Siemens IO-Link module (ET 200eco) with a different form factor and pinout. The 3RK5010-0BA10-0AA0 is a K20 module for the motor starter ecosystem — verify wiring and mechanical fit before specifying as a substitute.

MPN
3RK5010-0BA10-0AA0