Skip to main content
Siemens 3RS7000-2CE00 — Time Delay Relays

Siemens 3RS7000-2CE00 SIRIUS Signal Converter, 0-10V Input,

MPN3RS7000-2CE00
Active

Siemens SIRIUS single-range signal converter, 3RS7000-2CE00, 0-10 V input, 24 V AC/DC supply, 1 channel, snap-on mounting, IP20.

$300.89Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RS7000-2CE00 — Identification
ParameterValue
Product designationSingle-range converters
3RS7000-2CE00 — Electrical
ParameterValue
Rated surge voltage withstand2 500 V
3RS7000-2CE00 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-40 ... +80 °C
Transport temperature range-40 ... +80 °C
Operating humidity range10 ... 95 %
IP protection ratingIP20
Max. installation altitude2 000 m
Shock resistance (IEC 60068-2-27)sinusoidal half-wave 15g / 11 ms
Vibration resistance (IEC 60068-2-6)6 ... 150 Hz: 2 g
ESD immunity (IEC 61000-4-2)6 kV contact discharge / 8 kV air discharge
Burst immunity (IEC 61000-4-4)1 kV 5/50 ns
3RS7000-2CE00 — Mechanical
ParameterValue
Fastening methodsnap-on mounting
Mounting positionany
Width6.2 mm
Height93 mm
Depth72.5 mm
Wire range, solid (AWG)20 ... 14
Wire range, stranded (AWG)20 ... 14
Wire range, finely stranded w/ ferrule (mm²)0.25 ... 1.5 mm²
Clearance, rear0 mm
Clearance, front0 mm
Clearance, sides0 mm
Clearance, top0 mm
Clearance, bottom0 mm

Product details

The Siemens 3RS7000-2CE00 is a SIRIUS single-range signal converter that takes a 0... 10 V input and provides an isolated output, powered by a 24 V AC/DC supply.

The 0.8... 1.1 range at DC and at AC 50/60 Hz defines the adjustable threshold window for the input signal — you set the switching point within that band relative to the 0-10 V input. The 30 V input voltage rating is the maximum continuous input the converter can tolerate. With a rise time of 6 ms, this converter is suited for monitoring applications where a few milliseconds of delay are acceptable, not for high-speed counting or fast fault detection. The 72.5 mm depth and 93 mm height are standard for this class of SIRIUS component, so it aligns with adjacent devices on the rail. It consumes 0.29 W active power, negligible for panel power budgeting. The LED display version gives a visual status indication on the front.

Signal converters like this one are used in control panels to translate a sensor or transmitter's voltage output (0-10 V) into an isolated signal for a PLC analog input, or to condition a signal for a display or recorder. The galvanic isolation between input and output breaks ground loops and protects the receiving device. The any mounting position flexibility simplifies panel layout.

Frequently asked questions

What are the key ratings for this signal converter?

It accepts a 0-10 V input, operates on 24 V AC/DC supply, has a single channel with galvanic isolation between input and output, and snaps onto a DIN rail in a 6.2 mm wide slot. The adjustable threshold range is 0.8... 1.1 at DC and AC 50/60 Hz.

What is the mounting and clearance requirement?

It snaps onto a 35 mm DIN rail and requires 0 mm clearance upwards, downwards, forwards, backwards, and at the sides, so it can be mounted flush with adjacent components.

MPN
3RS7000-2CE00