It draws a 24 V AC coil at 50 or 60 Hz and carries a rated operating current of 10 A at 24 V. The screw-type terminals on the main current circuit accept solid or stranded wire: 2x 0.5–1.5 mm², 2x 0.75–2.5 mm², and up to 2x 0.75–4 mm². That covers standard control wiring without needing ferrules for the smaller strands, which saves a step during panel build.
Rated for the environment it lives in
The IP20 finger-safe protection on the front and terminals is standard for panel-mount gear — it keeps probing fingers out but is not rated for washdown. Pollution degree 3 means it tolerates conductive dust and humidity typical of industrial environments: cement plants, foundries, chemical processing. Maximum installation altitude is 2 000 m, so it works at most plant sites without derating.