Skip to main content
Siemens 3RT1015-1AF01-ZX95 — Contactors

Siemens SIRIUS 3RT1015-1AF01-ZX95 Power Contactor, Size S00,

MPN3RT1015-1AF01-ZX95

Siemens SIRIUS power contactor, Size S00, 3RT1015-1AF01-ZX95, 45 mm wide, screw terminals, 10 A at 24 V, 4 kW at 690 V, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1015-1AF01-ZX95 — Identification
ParameterValue
Contactor frame sizeS00
3RT1015-1AF01-ZX95 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V6.5 A
Rated value @ 400 V3 A
Rated value @ 500 V3.5 kW
Rated value @ 690 V4 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1015-1AF01-ZX95 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz110 V
3RT1015-1AF01-ZX95 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1015-1AF01-ZX95 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 35 A
Short-circuit coordination type 2, fusefuse gL/gG: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1015-1AF01-ZX95 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1015-1AF01-ZX95 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1015-1AF01-ZX95 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1015-1AF01-ZX95 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth72 mm

Product details

It measures 45 mm wide by 57.5 mm tall by 72 mm deep, so it tucks into tight DIN-rail enclosures without hogging space. The screw terminals accept solid or stranded wire: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) per clamp.

For motor switching, the AC-2 rating at 400 V is 3 kW, and the AC-4 rating at 400 V is 6.5 A — that's the figure that matters for reversing or inching duty, where the contactor makes and breaks stalled-rotor current. At 690 V it handles 4 kW, and at 500 V it handles 3.5 kW. The coil operates on 50/60 Hz at 0.8 to 1.1 times rated voltage (50 Hz) or 0.85 to 1.1 (60 Hz).

Where you'll use it — panel and environment

Side-by-side mounting is allowed without derating, so you can gang several contactors in a row. The front and terminals are rated IP20 — finger-safe for a panel, but not for washdown. Maximum installation altitude is 2000 m. Mechanical life is typical 30 million operations.

Frequently asked questions

What are the key ratings for motor switching?

AC-2 at 400 V: 3 kW. AC-4 at 400 V: 6.5 A. At 690 V: 4 kW. At 500 V: 3.5 kW. The coil accepts 50/60 Hz at 0.8...1.1 times rated voltage.

What is the physical size and mounting?

45 mm wide, 57.5 mm tall, 72 mm deep. Snaps onto 35 mm DIN rail per EN 50022. Side-by-side mounting is permitted.

What wire sizes does the screw terminal accept?

Solid or stranded: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) per terminal.

What is the operating temperature range?

-25 to +60 °C during operation. Pollution degree 3. Maximum altitude 2000 m.

MPN