It mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 50022, fitting into a 45 mm wide slot with a depth of 72 mm and height of 57.5 mm — a standard footprint for panel integration. The coil is rated for 24 VDC, and the contactor carries a rated operating current of 10 A at 24 V (AC-12), 6 A at 230 V, and 3 A at 400 V. For motor duty, it delivers 3 kW at 400 V in AC-2 service and 6.5 A in AC-4 at 400 V. At 690 V, the rated power reaches 4 kW.
Termination and Coordination