Mechanical life of 30 million cycles means this part outlasts the machine it's in for most light-duty conveyor or pump applications.
Screw terminals on both main and auxiliary circuits — solid or stranded wire from 0.5 to 4 mm², or AWG 20 to 12. Strip length is your call, but 8–10 mm is typical for these cages. Pollution degree 3 means it's fine in a standard industrial panel without conformal coating.
For type 2 coordination (no contactor welding on a short), Siemens calls for a 20 A gL/gG fuse. For type 1 coordination, a 35 A gL/gG fuse is enough. The coil draws 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V — standard AC/DC pickup values for this frame.