Siemens SIRIUS 3RT1015-1AV02 Power Contactor, Size S00, 24 V

MPN3RT1015-1AV02

Siemens SIRIUS, power contactor, 3RT1015-1AV02, Size S00, 24 VDC coil, 10 A rated operational current at AC-12, screw terminals, IP20, -25 to +60 °C.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1015-1AV02 — Identification
ParameterValue
Contactor frame sizeS00
3RT1015-1AV02 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V6.5 A
Rated value @ 400 V3 A
Rated value @ 500 V3.5 kW
Rated value @ 690 V4 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1015-1AV02 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz400 V
3RT1015-1AV02 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1015-1AV02 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 35 A
Short-circuit coordination type 2, fusefuse gL/gG: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1015-1AV02 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, solid or stranded2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Side-by-side mountingYes
3RT1015-1AV02 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1015-1AV02 — Environmental
ParameterValue
Installation altitude, max.2 000 m
3RT1015-1AV02 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth72 mm

Product details

It's rated for 10 A operational current at AC-12 duty (resistive) at 24 V, and delivers 3 kW at AC-2 (slip-ring motor) or 3.5 kW at 500 V, 4 kW at 690 V for standard three-phase induction motors. The 24 VDC coil pulls in reliably across the full rated control range.

The 10 A AC-12 rating covers resistive heater or lighting banks up to that current. Size S00 frame keeps the footprint tight at 45 mm wide, 57.5 mm tall, and 72 mm deep — fits standard 35 mm DIN rail per EN 50022 and allows side-by-side stacking for dense panel layouts.

Screw-type terminals on both main and auxiliary circuits accept solid or stranded copper: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²). AWG equivalents are 2x (20 to 16), 2x (18 to 14), or 1x 12. IP20 finger-safe protection on the front and terminals means it's suitable for enclosed panels where operators might reach in for adjustments — no special guarding needed for incidental contact.

Frequently asked questions

What are the key ratings for this contactor?

Rated 10 A at AC-12 (resistive) at 24 V, 3 kW at AC-2 at 400 V, 6.5 A at AC-4 at 400 V, and motor ratings of 3.5 kW at 500 V and 4 kW at 690 V. Coil pull-in range is 0.8 to 1.1 at 50 Hz, 0.85 to 1.1 at 60 Hz. Ambient temperature range is -25 to +60 °C.

What wire sizes does the screw terminal accept?

Solid or stranded: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²). AWG equivalents: 2x (20 to 16), 2x (18 to 14), or 1x 12.

What is the physical size and mounting?

Size S00 frame, 45 mm wide, 57.5 mm tall, 72 mm deep. Mounts via screw and snap-on onto 35 mm DIN rail per EN 50022. Side-by-side mounting is supported.

What short-circuit protection is required?

Type 2 coordination requires a 20 A gL/gG fuse; Type 1 coordination requires a 35 A gL/gG fuse.

MPN