SIRIUS S00 power contactor — 24 V DC coil, 10 A rated
Its 24 V DC coil draws the contactor in, and the built-in RC surge suppressor handles the inductive kickback — one less component to panel-build around. Rated at 10 A for DC-12 / AC-12 duty at 24 V, it also carries a 3 kW motor load in AC-2 category at 400 V and 6.5 A in AC-4 reversing duty at 400 V. Side-by-side mounting is permitted, and the IP20 finger-safe front terminals accept screw-type wiring up to 2x 4 mm² stranded.
Coordination and environment
Type 2 coordination with a gL/gG fuse rated 20 A is specified — that fuse clears a fault before the contactor welds, so the starter stays reusable after a short circuit. At 57.5 mm tall, it clears most 100 mm tall DIN-rail backplates. Terminal capacity covers 0.5 to 4 mm² stranded — common for motor circuits up to 4 kW.