It carries a 24 VAC coil rated at 50 Hz and 60 Hz, with a rated operational current of 10 A at 24 V. AC-4 at 400 V is 6.5 A, covering plugging and inching applications where the contactor opens under load. For motor switching at 500 V, it's rated for 3.5 kW; at 690 V, 4 kW. The spring-loaded terminals accept 2x (0.25 to 2.5 mm²) solid or stranded wire, which is the standard range for control-circuit wiring in a panel — no special lugs needed.
Integration notes
The contactor measures 45 mm wide, 60 mm high, and 73 mm deep. Side-by-side mounting is allowed without derating. Mechanical life is typical 30 million operations, which outlasts most contactors in this frame size for frequent cycling applications like conveyor start/stop or valve actuation. The coil draws power only during the closed state — no continuous holding current beyond the coil's rated VA.