It mounts via screw or snap-on onto a 35 mm DIN rail per EN 50022, and the main circuit connects through spring-loaded terminals that accept 2x (0.25 to 2.5 mm²) solid or stranded wire. The 24 VDC coil is rated for 10 A at 24 V, and the contactor handles motor loads up to 4 kW at 690 V or 3.5 kW at 500 V.
At 45 mm wide, 60 mm tall, and 73 mm deep, this S00 contactor fits the standard DIN-rail footprint. Side-by-side mounting is allowed, with a 6 mm clearance needed at the side for heat dissipation.
For resistive loads (AC-12), the maximum operating current is 10 A. Short-circuit protection requires a gL/gG fuse: 20 A for type 2 coordination, 35 A for type 1. Electrical life will be lower and depends on the switched current and duty cycle. The spring-loaded terminals accept AWG 24 to 14 conductors, which covers most panel wiring.