It carries a 3 kW rating at 400 V in AC-2 duty (slip-ring motors, reversing starts) and 6.5 A in AC-4 duty (plugging, inching). Wiring is through spring-loaded terminals on the main current circuit, accepting 2x (0.25... 2.5 mm²) solid or stranded, or 2x (24... 14) AWG. Strip length is not listed here, but spring-cage terminals typically need 8–10 mm — verify against the terminal marking before production wiring.
This matters for selectivity studies in the panel — the fuse size upstream must match the coordination type you're designing to. The auxiliary contact ratings cover a range of control voltages: 10 A at 24 V, 6 A at 230 V, 0.3 A at 220 V DC. If you're switching a 24 VDC PLC output, the 10 A rating gives plenty of headroom; at 110 VDC the contact is rated 1 A, so watch the inductive load curve.