The 45 mm width and 60 mm height fit standard panel layouts; depth is 73 mm. Spring-loaded terminals on both the main and auxiliary/control circuits accept 2x (0.25... 2.5 mm²) solid or stranded wire, or 2x (24... 14) AWG. No screwdriver needed for termination — just strip and push.
Rated operational voltage is 400 V at 50/60 Hz. For AC-3 motor switching, the contactor delivers 3.5 kW at 500 V and 4 kW at 690 V. The AC-4 rating (reversing/inching duty) is 6.5 A at 400 V. For resistive loads (AC-1), the 24 V rated current is 10 A; at 230 V it's 6 A; at 400 V it's 3 A. The DC switching capability is limited: 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V — so don't use this for high-current DC loads. Type 1 coordination (fault cleared but contactor may need replacement) requires a 35 A fuse.
RoHS compliance date is July 1, 2006, so it meets EU substance restrictions.