SIRIUS 3RT1015-2BE41 — 24 VDC Coil Power Contactor, Size S00
The main circuit uses spring-loaded terminals, accepting 2x (0.25... 2.5 mm²) solid or stranded wire, so no screwdriver needed for the power connections. Rated operational current is 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V. For motor duty at AC-2 at 400 V it's rated 3 kW; at AC-4 at 400 V it delivers 6.5 A. The 24 VDC coil draws 3.3 W holding power — a steady, low draw that keeps the panel power supply budget predictable.
For type 1 coordination (contactor may need replacement after fault), the fuse can be 35 A. That gives the panel designer a clear choice between protection level and fuse size.