SIRIUS 3RT1015-2BF41 — 110 VDC Coil, Spring-Loaded, Size S00
The 110 VDC coil draws 3.3 W during both closing and holding. Pick-up voltage is 0.85 × rated; drop-out is 1.1 × rated.
Termination and Mounting
Both main and control circuits use spring-loaded terminals, accepting 2x (0.25 … 2.5 mm²) solid or stranded — no screw torque to verify, no loosening under vibration.
Switching Ratings and Duty
Rated operational current at AC-12 (resistive) is 10 A maximum. For motor loads: AC-2 at 400 V delivers 3 kW; AC-4 at 400 V delivers 6.5 A. DC switching is specified per voltage: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V. Mechanical endurance is 30 million cycles — a long-life figure for a size S00 frame, suitable for high-cycle conveyor or pump applications where the contactor operates frequently.
Type 2 coordination (contactor remains usable after clearing the fault) requires a 20 A gL/gG fuse.