The coil draws 3.3 W both at closing and holding, so there's no inrush spike to budget for on the DC supply — a steady 3.3 W load from pickup through dropout. Rated for AC-3 duty at 3.5 kW on a 500 V line and 4 kW at 690 V, this contactor handles typical three-phase induction motors in that power band. For resistive or lightly inductive loads (AC-1), the continuous current rating is 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V — useful for heater banks or transformer primary switching.
Spring-loaded terminals accept 2x (0.25 to 2.5 mm²) solid or stranded wire, or 2x (24 to 14 AWG). The 6 mm clearance to adjacent components at the side is the minimum air gap for the rated insulation.