Skip to main content
Siemens 3RT1016-1AB01 — Contactors

Siemens SIRIUS 3RT1016-1AB01 Power Contactor, S00, 24 V 50 H

MPN3RT1016-1AB01

Siemens SIRIUS 3RT1016-1AB01 power contactor, size S00, 24 V 50/60 Hz coil, 4.5 kW at 500 V, screw terminals, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RT1016-1AB01 — Identification
ParameterValue
Contactor frame sizeS00
3RT1016-1AB01 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V4.5 kW
Rated value @ 690 V5.5 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1016-1AB01 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz24 V
3RT1016-1AB01 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1016-1AB01 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 35 A
Short-circuit coordination type 2, fusefuse gL/gG: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1016-1AB01 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, solid or stranded2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Side-by-side mountingYes
3RT1016-1AB01 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1016-1AB01 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Installation altitude, max.2 000 m
3RT1016-1AB01 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth72 mm

Product details

Siemens SIRIUS 3RT1016-1AB01 — Integrator's Spec Recap

The Siemens SIRIUS 3RT1016-1AB01 is a size S00 power contactor rated for a 24 V 50 Hz coil, switching motor loads up to 4.5 kW at 500 V. The AC-3 rating at 400 V is 4 kW — that's the number for standard squirrel-cage motor starting. Front and terminal faces carry IP20 protection, so it's suited for enclosed panel installation where accidental finger contact is the concern. Pollution degree 3 means it handles conductive pollution in industrial environments — standard for control panels near production floors.

Terminal & Wiring Detail

Both main and auxiliary circuits use screw-type terminals. The main contact wiring accepts solid conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²). AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12. Auxiliary contacts share the same wire range. For fuse coordination, type 2 coordination (no damage) requires a 20 A gL/gG fuse; type 1 coordination (damage allowed, no fire risk) allows a 35 A gL/gG fuse.

Coil Operating Range & Ratings

The coil is rated at 24 V at 50 Hz, with an operating range of 0.8 to 1.1 times rated voltage at 50 Hz, and 0.85 to 1.1 at 60 Hz. The coil draw at various control voltages: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V, 6 A at 230 V, and 3 A at 400 V — these are inrush or holding values depending on the circuit design.

Frequently asked questions

What is the closest functional alternative to the 3RT1016-1AB01?

The 3RT1017-1AP01 is a functional peer within the same SIRIUS S00 frame. The key difference is the coil voltage: the 3RT1016-1AB01 uses a 24 V 50 Hz coil, while the 3RT1017-1AP01 uses a different coil voltage. Verify coil compatibility before substituting — the mounting footprint and terminal layout are identical.

What are the mounting dimensions for the 3RT1016-1AB01?

The contactor measures 45 mm wide by 57.5 mm high by 72 mm deep. It snaps onto a 35 mm DIN rail per EN 50022.

What wire sizes does the 3RT1016-1AB01 accept?

Main and auxiliary screw terminals accept solid conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²). AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12.

What fuse coordination is required for the 3RT1016-1AB01?

For type 2 coordination (no damage to the contactor), use a 20 A gL/gG fuse. For type 1 coordination (damage allowed, no fire or shock hazard), a 35 A gL/gG fuse is permitted.

MPN
3RT1016-1AB01