Skip to main content
Siemens 3RT1016-1AB01-ZW95 — Contactors

Siemens 3RT1016-1AB01-ZW95 SIRIUS Power Contactor, S00, 24V

MPN3RT1016-1AB01-ZW95

Siemens SIRIUS 3RT1016-1AB01-ZW95 power contactor, size S00, 24 V 50/60 Hz coil, screw-type terminals, IP20 front, 45 mm width.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1016-1AB01-ZW95 — Identification
ParameterValue
Contactor frame sizeS00
3RT1016-1AB01-ZW95 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V4.5 kW
Rated value @ 690 V5.5 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1016-1AB01-ZW95 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz24 V
3RT1016-1AB01-ZW95 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1016-1AB01-ZW95 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 35 A
Short-circuit coordination type 2, fusefuse gL/gG: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1016-1AB01-ZW95 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1016-1AB01-ZW95 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1016-1AB01-ZW95 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1016-1AB01-ZW95 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth72 mm

Product details

SIRIUS S00 Power Contactor, 24 V Coil

It carries a 24 V 50/60 Hz coil, draws its control voltage from a standard 24 V supply, and terminates main circuit wiring through screw-type terminals. Rated operational current at 400 V is 3 A, and at 690 V it delivers 5.5 kW, making it suited for smaller three-phase motors, contactor banks, or auxiliary switching duties where the S00 footprint fits.

The AC-2 rating at 400 V is 4 kW, covering wound-rotor motor starting; the AC-4 rating at 400 V is 8.5 A, which governs plugging and inching duty cycles. For resistive loads, the AC-12 maximum operating current is 10 A.

Main circuit terminals accept solid conductors from 2x (0.5 to 1.5 mm²) up to 2x (0.75 to 4 mm²), or stranded equivalents, with AWG sizes from 2x (20 to 16) up to 1x 12. Auxiliary contact configuration is 1 NO instantaneous contact, which can be used for feedback to a PLC or to seal in the coil circuit.

Short-Circuit Coordination

This guides the upstream protection selection when the contactor is part of a motor branch circuit.

For BOM freeze or AML adherence, the 3RT1016-1AB01-ZW95 is a standard catalog item from Siemens SIRIUS family — no deviation needed if it is on the customer's approved vendor list.

Frequently asked questions

What are the key ratings for this contactor?

It has a 24 V 50/60 Hz coil, rated operational current of 3 A at 400 V, and delivers 5.5 kW at 690 V. AC-4 rating is 8.5 A at 400 V, and AC-12 maximum is 10 A. Mechanical life is 30,000,000 cycles typical.

What wire sizes does the screw terminal accept?

Solid conductors from 2x (0.5 to 1.5 mm²) up to 2x (0.75 to 4 mm²), with stranded equivalents. AWG sizes range from 2x (20 to 16) up to 1x 12.

What is the mounting method and panel footprint?

It mounts via screw or snap-on onto a 35 mm DIN rail per EN 50022, with dimensions of 45 mm width, 57.5 mm height, and 72 mm depth. Side-by-side mounting is permitted.

What short-circuit protection is required?

For Type 1 coordination, use a 35 A gL/gG fuse; for Type 2 coordination (no damage to the contactor), use a 20 A gL/gG fuse.

MPN
3RT1016-1AB01-ZW95