Skip to main content
Siemens 3RT1016-1AD02 — Contactors

Siemens 3RT1016-1AD02 SIRIUS Power Contactor, S00, 24 VDC, 1

MPN3RT1016-1AD02

Siemens SIRIUS 3RT1016-1AD02 power contactor, size S00, 24 VDC coil, screw terminals, 45 mm wide, IP20 front protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1016-1AD02 — Identification
ParameterValue
Contactor frame sizeS00
3RT1016-1AD02 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V4.5 kW
Rated value @ 690 V5.5 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1016-1AD02 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz42 V
3RT1016-1AD02 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1016-1AD02 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 35 A
Short-circuit coordination type 2, fusefuse gL/gG: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1016-1AD02 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1016-1AD02 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1016-1AD02 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1016-1AD02 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth72 mm

Product details

Rated for a 24 VDC coil, it pulls in at 10 A on the main contacts at that voltage, and can handle up to 4.5 kW at 500 V or 5.5 kW at 690 V. The mechanical life is typical 30,000,000 cycles, so it's built for high-cycle lines.

The screw terminals accept solid or stranded conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and up to 2x (0.75 to 4 mm²) maximum. AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12. For short-circuit protection, type 2 coordination requires a 20 A gL/gG fuse; type 1 coordination allows a 35 A gL/gG fuse.

The coil operates at 0.8 to 1.1 times rated voltage at 50 Hz, and 0.85 to 1.1 at 60 Hz.

Frequently asked questions

What are the key ratings for this contactor?

The 24 VDC coil draws 10 A on the main contacts at that voltage. Motor power ratings are 4.5 kW at 500 V and 5.5 kW at 690 V. AC-4 motor duty at 400 V is 8.5 A. Mechanical life is typical 30,000,000 cycles.

What wire sizes does the screw terminal accept?

Solid or stranded: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), max 2x (0.75 to 4 mm²). AWG: 2x (20 to 16), 2x (18 to 14), 1x 12.

What is the physical size of the 3RT1016-1AD02?

Width 45 mm, height 57.5 mm, depth 72 mm. It mounts on a 35 mm DIN rail per DIN EN 50022.

What short-circuit protection is required?

Type 2 coordination: 20 A gL/gG fuse. Type 1 coordination: 35 A gL/gG fuse.

MPN
3RT1016-1AD02