Rated for a 24 VDC coil, it pulls in at 10 A on the main contacts at that voltage, and can handle up to 4.5 kW at 500 V or 5.5 kW at 690 V. The mechanical life is typical 30,000,000 cycles, so it's built for high-cycle lines.
The screw terminals accept solid or stranded conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and up to 2x (0.75 to 4 mm²) maximum. AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12. For short-circuit protection, type 2 coordination requires a 20 A gL/gG fuse; type 1 coordination allows a 35 A gL/gG fuse.
The coil operates at 0.8 to 1.1 times rated voltage at 50 Hz, and 0.85 to 1.1 at 60 Hz.