Rated operational current at 24 V is 10 A (AC-12), and at 230 V it carries 6 A. For motor duty, the AC-2 rating at 400 V is 4 kW, and the AC-4 rating at 400 V is 8.5 A. The control supply coil accepts 0.8 to 1.1 times the rated voltage at both 50 Hz and 60 Hz, with a rated value of 230 V at 50 Hz and 230 V at 60 Hz. Pollution degree 3 rating suits industrial environments.
The terminal accepts solid conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and a maximum of 2x (0.75 to 4 mm²). For AWG, it accepts 2x (20 to 16), 2x (18 to 14), and 1x 12. This allows dense packing on the DIN rail while maintaining thermal separation. The contactor has one instantaneous contact.
For type of coordination 1, the required fuse is gL/gG 35 A. For type of coordination 2, the required fuse is gL/gG 20 A. This distinction matters for selectivity studies: coordination 1 allows the contactor to be damaged after a short circuit (but no fire risk), while coordination 2 keeps the contactor operational after clearing the fault. The mechanical endurance is typical 30 million operations, which reflects the S00 frame's suitability for high-cycle applications.