Siemens 3RT1016-1AP02-ZW97 — Contactors

Siemens SIRIUS 3RT1016-1AP02-ZW97 Power Contactor, S00 Frame

MPN3RT1016-1AP02-ZW97

Siemens SIRIUS 3RT1016-1AP02-ZW97 power contactor, size S00, 45 mm width, 72 mm depth, screw-type terminals, 4.5 kW at 500 V / 5.5 kW at 690 V motor rating.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1016-1AP02-ZW97 — Identification
ParameterValue
Contactor frame sizeS00
3RT1016-1AP02-ZW97 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V4.5 kW
Rated value @ 690 V5.5 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1016-1AP02-ZW97 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz230 V
3RT1016-1AP02-ZW97 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1016-1AP02-ZW97 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 35 A
Short-circuit coordination type 2, fusefuse gL/gG: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1016-1AP02-ZW97 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1016-1AP02-ZW97 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1016-1AP02-ZW97 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1016-1AP02-ZW97 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth72 mm

Product details

The front face carries IP20 protection; the terminals themselves are also rated IP20, so the part is suited for enclosed panel use where no washdown or dust ingress is expected.

Rated for motor switching at 4.5 kW on a 500 V 50 Hz supply and 5.5 kW at 690 V, this contactor handles typical three-phase induction motors up to that power band — think small conveyors, pumps, or fan drives. The AC-2 rating at 400 V gives 4 kW, which is the duty for slip-ring motors; the AC-4 rating at 400 V is 8.5 A, covering reversing or inching applications where the contactor makes and breaks under load. For DC switching, the 24 V coil draws 10 A, dropping to 2 A at 60 V and 0.3 A at 220 V — useful for braking or DC injection circuits.

Main circuit terminals are screw-type, accepting 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) solid or stranded copper — the range covers most control panel wiring from signal-level to motor feeder. Type 1 coordination (contactor may need replacement after fault) allows a 35 A fuse.

The 57.5 mm height keeps it below common enclosure gland-plate clearances.

Frequently asked questions

What is the closest functional alternative to this contactor?

The 3RT1016-2AP02 is the same base frame size S00 with similar electrical ratings but uses spring-cage terminals instead of screw-type. If your panel wiring is already spec'd for screw terminals, the -1AP02 variant is the direct fit; the -2AP02 would require a terminal adapter or re-termination at the panel level.

What are the key dimensions for panel layout?

Width is 45 mm, height is 57.5 mm, and depth is 72 mm. It mounts on a 35 mm DIN rail per EN 50022, and side-by-side mounting is allowed without additional spacing.

What wire sizes does the screw terminal accept?

The main circuit terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) solid or stranded copper. For AWG, it accepts 2x (20 to 16), 2x (18 to 14), or 1x 12.

What short-circuit protection is required?

For Type 2 coordination (no damage to the contactor), use a gL/gG fuse rated at 20 A. For Type 1 coordination (contactor may be damaged), a 35 A fuse is permitted.