Depth is 114 mm, which clears most enclosure depths. Screw-type terminals on the main circuit accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) solid or stranded wire, with AWG equivalents of 2x (20 to 16), 2x (18 to 14), and 1x 12.
Ratings and coordination
Rated for AC-2 duty at 400 V delivering 4 kW, and AC-4 at 400 V with 8.5 A switching current. For motor loads at 500 V, it handles 4.5 kW; at 690 V, 5.5 kW. The coil operates at 50/60 Hz with voltage tolerance of 0.8 to 1.1 at 50 Hz and 0.85 to 1.1 at 60 Hz. For short-circuit protection, Type 2 coordination requires a 20 A gL/gG fuse; Type 1 allows up to 35 A gL/gG.