For motor duty, the contactor is rated 4.5 kW at 500 V and 5.5 kW at 690 V. Auxiliary contact block provides 3 instantaneous contacts, rated 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V, among other voltage taps. This covers feedback to a PLC or holding-circuit interlocking without an add-on block.
Main circuit terminals are screw-type, accepting 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) solid or stranded conductors. AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12. This covers typical motor feeder cables up to 4 mm² without needing lug adapters. The contactor occupies 45 mm width, 57.5 mm height, and 114 mm depth. Side-by-side mounting is permitted with zero side clearance, so multiple units pack tightly on the DIN rail. For short-circuit coordination, Type 1 coordination requires a 35 A gL/gG fuse; Type 2 coordination requires a 20 A gL/gG fuse. This determines the upstream protective device selection for the panel schedule.
Mechanical service life is typical 30,000,000 operations, which reflects the contactor's endurance in high-cycle applications like conveyor or packaging machinery. The operating voltage range factor is 0.8 to 1.1 at 50 Hz and 0.85 to 1.1 at 60 Hz, meaning the coil holds in across a sag down to 80% of nominal at 50 Hz, and 85% at 60 Hz.