Skip to main content
Siemens 3RT1016-1AT61 — Contactors

Siemens 3RT1016-1AT61 SIRIUS S00 Power Contactor, 3-Pole, 10

MPN3RT1016-1AT61

Siemens SIRIUS S00 power contactor, 3RT1016-1AT61, 3-pole NO, 10 A AC-12, 4 kW AC-2 at 400 V, screw terminals, 45 mm width, IP20 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1016-1AT61 — Identification
ParameterValue
Contactor frame sizeS00
3RT1016-1AT61 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V4.5 kW
Rated value @ 690 V5.5 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1016-1AT61 — Control & Coil
ParameterValue
Control supply voltage typeAC
3RT1016-1AT61 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1016-1AT61 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 35 A
Short-circuit coordination type 2, fusefuse gL/gG: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1016-1AT61 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1016-1AT61 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1016-1AT61 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1016-1AT61 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth72 mm

Product details

It carries a 10 A maximum operating current in AC-12 duty (resistive), and 4 kW at 400 V in AC-2 duty (slip-ring motors).

Switching ratings and duty classes

The 3RT1016-1AT61 is rated across multiple duty classes and voltages. For AC-2 at 400 V, it switches 4 kW; for AC-4 at 400 V, the rated operating current is 8.5 A. At 690 V, the motor rating is 5.5 kW. The contactor also handles DC switching: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V. The AC-12 resistive rating of 10 A sets the ceiling for general-purpose load switching.

Short-circuit coordination and terminal details

Main circuit terminals are screw-type, accepting 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) solid or stranded conductors. AWG equivalents are 2x (20 to 16), 2x (18 to 14), or 1x 12.

Environmental limits and protection

Operating temperature -25 °C to +60 °C. Rated for installation up to 2,000 m altitude. IP20 front and terminal protection. Pollution degree 3. Mechanical endurance 30,000,000 operations typical.

MPN
3RT1016-1AT61