It carries motor power ratings up to 4.5 kW at 500 V and 5.5 kW at 690 V, covering common three-phase induction motors in that frame.
Width is 45 mm, so it occupies one standard 45 mm module slot. Screw-type terminals on the main circuit accept 2x (0.5 to 1.5 mm²) solid or 2x (0.75 to 2.5 mm²) stranded, with a maximum of 2x (0.75 to 4 mm²). That covers typical panel wiring up to 4 mm² without needing lug adapters. The front face is IP20, so finger-safe when installed in an enclosure.
Altitude rating to 2 000 m means no derating needed for most installations below that elevation. Short-circuit coordination is specified: Type 2 coordination requires a gL/gG 20 A fuse, Type 1 allows up to 35 A. That gives the panel builder a clear fuse size for selectivity without guesswork.
Auxiliary contacts and coil data
One instantaneous auxiliary contact is built in (NO or NC configuration depends on the variant — the base part carries one auxiliary contact block). The coil operates at 0.85 to 1.1 times the rated voltage, so it picks up reliably at 20.4 VDC and holds through 26.4 VDC.