The 24 VDC coil draws a closing and holding power of 3.3 W, with a pickup threshold of 0.85x rated voltage and a dropout at 1.1x, so the coil reliably engages above 20.4 V and releases above 26.4 V. For main contact switching, the AC-3 motor rating reaches 4.5 kW at 500 V and 5.5 kW at 690 V — the rating that governs real motor starts. The auxiliary contact block is a single instantaneous contact (1 NO or 1 NC depending on wiring), sufficient for feedback to a PLC input or for a holding circuit.
It fits alongside other S00 components (overload relays, aux contact blocks) on the same DIN rail, with side-by-side mounting permitted at 6 mm spacing — no derating needed for ambient temperatures up to 60 °C. Screw-type terminals on the main circuit accept 2x (0.5…1.5 mm²), 2x (0.75…2.5 mm²), or max 2x (0.75…4 mm²) solid/stranded copper. The same range applies to the coil terminals. Strip length is not specified in this listing, but standard practice for this terminal family is 8–10 mm.
These values assume the main circuit is protected by a suitable motor-protective circuit breaker or fuse. The built-in varistor surge suppressor clamps the coil voltage spike on de-energization, which protects nearby PLC outputs and eliminates the need for an external flyback diode — a common oversight in panel wiring.