It carries a 24 VDC coil and is rated for 4.5 kW at 400 V in AC-3 duty, meaning it handles the inductive load of a standard three-phase motor up to that power. At 690 V the motor rating reaches 5.5 kW, so the same contactor can serve higher-voltage machines without upsizing the frame. The coil draws 1.4 W both on pick-up and hold, so the control transformer or DC supply sees a steady load — no inrush spike to size around. A built-in varistor suppresses the inductive kick from the coil, which simplifies panel wiring by eliminating the need for an external suppression diode or RC snubber across the coil terminals.
The S00 footprint is 45 mm wide, 57.5 mm tall, and 72 mm deep — a space-saving profile that leaves room for auxiliary contact blocks or an overload relay on the same rail. Screw-type terminals on the main circuit accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) solid or stranded copper.