Rated operational current is 10 A at 24 V, with AC-4 switching capability of 8.5 A at 400 V — that's the reversing or inching duty cycle that wears contacts fastest, so this rating tells you the contactor can handle frequent jogging or plugging without premature failure. At 500 V it's rated for 4.5 kW motor power, and at 690 V for 5.5 kW, covering standard European low-voltage motor circuits. Main and auxiliary circuits use spring-loaded terminals, accepting 2x (0.25 to 2.5 mm²) solid or stranded wire, or 2x (24 to 14 AWG). That's a tool-less connection — strip, push, done — which shaves minutes per termination on a multi-contactor panel.
The 45 mm wide footprint and 73 mm depth fit the Size S00 envelope, and side-by-side mounting is permitted with no derating gap — that's another SKU I don't need for spacing brackets.
For type 1 coordination (contactor may need replacement after fault), use gL/gG 35 A. That's the fuse spec your panel designer needs for the SCCR calculation.
RoHS compliance is confirmed by the substance prohibition date of 01.07.2006, covering the EU RoHS directive. No UL or CSA mark is listed in the spec record, so verify with the factory if your panel requires those for the destination jurisdiction.