Siemens SIRIUS 3RT1016-2AP01-1AA0 Power Contactor, S00, 4 kW

MPN3RT1016-2AP01-1AA0

Siemens SIRIUS 3RT1016-2AP01-1AA0, Size S00 power contactor, 4 kW at 400 V AC-3, 24 VDC coil, spring-loaded terminals, screw and snap-on mounting.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1016-2AP01-1AA0 — Identification
ParameterValue
Contactor frame sizeS00
3RT1016-2AP01-1AA0 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V4 kW
Rated value @ 500 V4.5 kW
Rated value @ 690 V5.5 kW
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1016-2AP01-1AA0 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz230 V
3RT1016-2AP01-1AA0 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1016-2AP01-1AA0 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 35 A
Short-circuit coordination type 2, fusefuse gL/gG: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1016-2AP01-1AA0 — Connection & Mounting
ParameterValue
Main circuit connectionspring-loaded terminals
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid2x (0.25 ... 2.5 mm²)
Conductor cross-section, solid or stranded2x (0,25 ... 2,5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.25 ... 1.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Side-by-side mountingYes
3RT1016-2AP01-1AA0 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1016-2AP01-1AA0 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Installation altitude, max.2 000 m
3RT1016-2AP01-1AA0 — Mechanical
ParameterValue
Width45 mm
Height60 mm
Depth73 mm

Product details

The Siemens SIRIUS 3RT1016-2AP01-1AA0 is a Size S00 power contactor rated for switching motor loads up to 4 kW at 400 V AC-3, with a 24 VDC coil. It's built for DIN-rail mounting on a 35 mm rail per DIN EN 50022, using either screws or the integrated snap-on feature — a standard fit for any industrial control panel.

The operational current at AC-12 (resistive load) is 10 A, which covers heater banks or lighting circuits where the inrush is minimal. For DC switching, the contactor is rated 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V — the voltage-dependent derating curve is steep because DC arcs are harder to extinguish. This matters for selectivity studies and fuse sizing in the panel.

Mounting and Integration Details

Side-by-side mounting is allowed with a 6 mm gap at the side for heat dissipation. Front-side protection is IP20, meaning it's finger-safe for the panel builder but not washdown-rated. Both main and auxiliary/control circuits use spring-loaded terminals, accepting 2x (0.25 to 2.5 mm²) solid or stranded wire, or 2x (24 to 14 AWG). No screwdriver torque check needed — the spring cage holds firm against vibration, which is a plus on a press line or conveyor drive.

Mechanical endurance is listed at 30 million operations — a high cycle count that suits frequent-start applications like conveyor systems or packaging lines.

Frequently asked questions

What are the key dimensions for panel layout?

The contactor is 45 mm wide, 60 mm high, and 73 mm deep. Side-by-side mounting requires a 6 mm gap between units.

What wire sizes does the spring-loaded terminal accept?

The spring-loaded terminals accept 2x (0.25 to 2.5 mm²) solid or stranded wire, or 2x (24 to 14 AWG).

What is the AC-4 rating for reversing duty?

The AC-4 rating at 400 V is 8.5 A. This is the current the contactor can switch for inching or plugging applications where the motor is re-energized while still rotating.

What short-circuit protection fuse is required for Type 2 coordination?

For Type 2 coordination (no damage to the contactor), use a gL/gG fuse rated 20 A. For Type 1 coordination, a 35 A fuse is allowed.