The 110 V DC coil draws 2.3 W for both closing and holding, and the integrated varistor suppresses the switching transient — no external suppressor needed on the coil circuit. Spring-loaded terminals on the main circuit accept 2x (0.25... 2.5 mm²) solid or stranded wire, so the wireman lands the power leads without a screwdriver. Rated for motor duty: at AC-3, 400 V it handles 4.5 kW; at 690 V, 5.5 kW. The AC-4 rating at 400 V is 8.5 A for reversing or inching applications where the contactor makes and breaks the load under full current.
At 45 mm wide and 73 mm deep, it fits a standard 45 mm slot in a motor starter row.
Type 1 coordination (contactor may need replacement after fault) allows a 35 A fuse. The coil circuit includes a varistor as standard — no extra surge suppressor to order.