Skip to main content
Siemens 3RT1017-1AB01-ZW97 — Contactors

Siemens 3RT1017-1AB01-ZW97 SIRIUS Contactor, S00, 5.5 kW at

MPN3RT1017-1AB01-ZW97

Siemens SIRIUS 3RT1017-1AB01-ZW97 power contactor, size S00, 45 mm wide, 5.5 kW at 500 V AC-3, screw terminals, IP20 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1017-1AB01-ZW97 — Identification
ParameterValue
Contactor frame sizeS00
3RT1017-1AB01-ZW97 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V5.5 kW
Rated value @ 690 V5.5 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1017-1AB01-ZW97 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz24 V
3RT1017-1AB01-ZW97 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1017-1AB01-ZW97 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 35 A
Short-circuit coordination type 2, fusefuse gL/gG: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1017-1AB01-ZW97 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1017-1AB01-ZW97 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1017-1AB01-ZW97 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1017-1AB01-ZW97 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth72 mm

Product details

The Siemens SIRIUS 3RT1017-1AB01-ZW97 is a size S00 power contactor rated for switching motor loads up to 5.5 kW at 500 V in AC-3 duty. The 45 mm width and 72 mm depth fit standard DIN-rail enclosures with 35 mm rail per DIN EN 50022, and the IP20 front protection means it's safe for finger contact in a closed panel.

The 5.5 kW rating at 500 V AC-3 is the motor-switching capability — that's the headline number for sizing. For high-stress applications like plugging or jogging, the AC-4 rating of 8.5 A at 400 V is the one to watch; it's lower than the AC-3 current because the contacts take more wear breaking stalled rotor current. Short-circuit coordination is specified: type 2 coordination requires a 20 A gL/gG fuse, type 1 allows a 35 A gL/gG fuse. Type 2 means the contactor remains usable after a fault — no contact welding — which matters for production lines where downtime for replacement is expensive.

The screw-type terminals for the main circuit accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) — or AWG equivalents 2x (20-16), 2x (18-14), and 1x 12. That's enough for the motor leads on a 5.5 kW drive at 500 V.

Frequently asked questions

What are the key ratings for this contactor?

It's rated 5.5 kW at 500 V AC-3 for motor switching, 8.5 A at 400 V AC-4 for high-stress duty, and 10 A at AC-12 for resistive loads. The coil is 24 V at 50/60 Hz.

What is the physical size and mounting?

Size S00 frame: 45 mm wide, 57.5 mm tall, 72 mm deep. It snaps onto 35 mm DIN rail per EN 50022 or can be screw-mounted. Side-by-side mounting needs 6 mm spacing.

What wire sizes does the screw terminal accept?

The main circuit terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) solid or stranded. AWG equivalents are 2x (20-16), 2x (18-14), and 1x 12.

What fuse coordination is specified?

Type 2 coordination requires a 20 A gL/gG fuse; type 1 allows a 35 A gL/gG fuse. Type 2 is preferred for production lines to avoid contact welding after a short circuit.

MPN
3RT1017-1AB01-ZW97