At 400 V AC-2 duty (slip-ring motors, moderate overloads) it handles 5.5 kW; at AC-4 (plugging, inching) the current limit is 8.5 A. The 24 V coil holds at 0.8–1.1× rated voltage at 50 Hz, 0.85–1.1 at 60 Hz — that 0.8× dropout margin means a saggy 19.2 V bus still keeps it closed. For resistive loads (AC-12) it switches 10 A maximum. The terminal block accepts up to 2× 4 mm² stranded or 1× 12 AWG, solid or ferruled.
This order code carries a current lifecycle status.
It mounts side-by-side without derating (6 mm clearance to adjacent devices). The terminals carry IP20 finger-safe protection.