Specifications

3RT1017-1AG11 — Identification
ParameterValue
Contactor frame sizeS00
3RT1017-1AG11 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V5.5 kW
Rated value @ 690 V5.5 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1017-1AG11 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz100 V
3RT1017-1AG11 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1017-1AG11 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 35 A
Short-circuit coordination type 2, fusefuse gL/gG: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1017-1AG11 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, solid or stranded2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Side-by-side mountingYes
3RT1017-1AG11 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1017-1AG11 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Installation altitude, max.2 000 m
3RT1017-1AG11 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth72 mm

Product details

Its 24 VDC coil is specified for a 0.8 to 1.1 x rated voltage hold range at 60 Hz, with a dropout threshold below 18 V typical for this class. The contactor carries AC-2 and AC-4 ratings at 400 V — 5.5 kW and 8.5 A respectively — so it handles moderate motor duty cycles like conveyors or pumps where frequent starts and reversals are expected. The 45 mm width and 72 mm depth leave room for adjacent devices in a crowded enclosure.

Auxiliary contact ratings and wiring

The auxiliary contact block switches 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V — these are the maximum continuous currents for the control circuit, not the main power path. For the main circuit, screw terminals accept solid or stranded wire from 2x 0.5 to 1.5 mm², 2x 0.75 to 2.5 mm², or up to 2x 4 mm² (max). AWG equivalents are 2x 20–16, 2x 18–14, and 1x 12. The auxiliary terminals share the same wire range. Type 1 and Type 2 coordination fuse requirements are specified: Type 2 requires a gL/gG 20 A fuse; Type 1 requires 35 A. This matters for selectivity design — if the panel requires Type 2 coordination to minimize downstream damage on a fault, size the upstream protection accordingly.

Frequently asked questions

What are the key ratings for 3RT1017-1AG11?

The contactor is size S00 with a 24 VDC coil. It is rated for AC-2 at 400 V at 5.5 kW and AC-4 at 400 V at 8.5 A. Auxiliary contacts switch 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V. Dimensions: 45 mm wide, 57.5 mm high, 72 mm deep.

Where can I buy 3RT1017-1AG11?

This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability; lead time and stock position are confirmed at quote time.

What wire sizes does 3RT1017-1AG11 accept?

Main and auxiliary screw terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) solid or stranded. AWG equivalents: 2x (20–16), 2x (18–14), and 1x 12.

MPN