Skip to main content
Siemens 3RT1017-1AH02-ZX95 — Contactors

Siemens 3RT1017-1AH02-ZX95 SIRIUS Contactor, S00, 5.5 kW at

MPN3RT1017-1AH02-ZX95

Siemens SIRIUS power contactor, size S00, 3RT1017-1AH02-ZX95, screw-type terminals, 5.5 kW at 690 V AC-3, IP20 finger-safe front, 45 mm wide, snap-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1017-1AH02-ZX95 — Identification
ParameterValue
Contactor frame sizeS00
3RT1017-1AH02-ZX95 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V5.5 kW
Rated value @ 690 V5.5 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1017-1AH02-ZX95 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz48 V
3RT1017-1AH02-ZX95 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1017-1AH02-ZX95 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 35 A
Short-circuit coordination type 2, fusefuse gL/gG: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1017-1AH02-ZX95 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1017-1AH02-ZX95 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1017-1AH02-ZX95 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1017-1AH02-ZX95 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth72 mm

Product details

It mounts via screw or snap-on onto a 35 mm DIN rail per EN 50022, fitting the standard panel footprint at 45 mm wide, 57.5 mm tall, and 72 mm deep. Rated for AC-3 duty at 5.5 kW on both 500 V and 690 V supplies, this contactor handles the inrush of squirrel-cage motors up to that load — the 690 V rating is what matters for 400/690 V delta-start or IT-grid installations. The contactor carries a mechanical life of 30,000,000 operations typical, with pollution degree 3 rated for conductive environments typical of industrial enclosures.

Main circuit wiring uses screw-type terminals accepting 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) solid or stranded conductors — AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12. The front face and terminals carry IP20 finger-safe protection, so the contactor can sit on an open panel door during commissioning without shock risk. Side-by-side mounting is permitted with zero side clearance, which saves rail space in dense panels. The 6 mm clearance noted is for the arc chamber — not between units when ganged. For short-circuit coordination, type 1 requires a 35 A gL/gG fuse upstream; type 2 coordination drops to a 20 A gL/gG fuse to limit let-through energy and preserve the contactor after a fault.

The integrated auxiliary contacts are rated 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V — enough for PLC inputs or small relay coils in the control circuit. The AC-12 rating of 10 A covers resistive loads like heater contactors or signal lamps.

Frequently asked questions

What are the key motor ratings for this contactor?

AC-3 duty: 5.5 kW at 500 V and 5.5 kW at 690 V. AC-4 (reversing/plugging): 8.5 A at 400 V. AC-2 (slip-ring motors): also 5.5 kW at 400 V.

What wire sizes does the screw terminal accept?

Solid or stranded: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), max 2x (0.75 to 4 mm²). AWG: 2x (20 to 16), 2x (18 to 14), 1x 12.

Can this contactor be mounted side-by-side with no gap?

Yes, side-by-side mounting is permitted. The 6 mm clearance noted is for the arc chamber, not between adjacent units on the rail.

What short-circuit protection is required?

Type 1 coordination: 35 A gL/gG fuse. Type 2 coordination: 20 A gL/gG fuse to limit damage after a fault.

MPN