Rated for AC-1 duty at 10 A, it handles resistive loads up to that current. For motor switching, the AC-4 rating at 400 V is 8.5 A, which covers smaller induction motors — think fractional-horsepower pumps, fans, or conveyors in a typical 400 V line. The coil is 24 VDC, a common control voltage in modern PLC-driven panels.
Integration and wiring
The S00 frame accepts up to 4 mm² stranded wire (max 2x 4 mm²) on the main terminals, which is adequate for the rated currents. Pollution degree 3 means it tolerates conductive dust typical of factory floors. This matters when sizing the upstream protective device in a motor branch circuit.