It mounts via screw or snap-on onto a 35 mm DIN rail per EN 50022, fitting into a 45 mm wide slot with a 57.5 mm height and 72 mm depth — the S00 footprint that panel builders know for high-density layouts.
Terminals, wiring, and coordination
Main circuit terminals are screw-type, accepting 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) solid/stranded conductors. AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12. This covers most motor-circuit wiring sizes up to 4 mm² without needing terminal adapters. These values guide the MCCB or fuse selection in the feeder circuit. Auxiliary contact ratings span the control voltage range: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 0.3 A at 220 V DC — enough for pilot-duty control circuits across common AC and DC supplies.
Front protection is IP20 — finger-safe terminals for the control panel environment. The contactor is rated for operation up to 2,000 m altitude without derating.
The part carries the SIRIUS brand and is part of the broad S00 contactor family. No last-time-buy or phase-out notice is in effect.