It is rated for AC-2 duty at 5.5 kW at 400 V, which means it handles wound-rotor motor starting and reversing up to that power level, and delivers 8.5 A in AC-4 duty for plugging and inching applications.
The AC-4 rating of 8.5 A at 400 V is lower than the AC-3 equivalent would be, reflecting the higher electrical wear from inching or reversing duty. Main circuit termination is screw-type terminals accepting 2x (0.5 to 1.5 mm²) solid, 2x (0.75 to 2.5 mm²) solid, or up to 2x (0.75 to 4 mm²) stranded. For AWG, that's 2x (20 to 16), 2x (18 to 14), or 1x 12. Type 1 coordination requires a 35 A gL/gG fuse; Type 2 coordination requires a 20 A gL/gG fuse.
Panel integration
Depth is 72 mm, height 57.5 mm, so it fits compactly in a 45 mm-wide DIN slot.